When it comes to your Chesterbrook, PA’s home heating, cooling and water heater systems, DiBiase Heating & Cooling Company makes sure they’re running at peak efficiency for your improved indoor comfort, convenience and safety.
This is a service promise and a reflection of our core values: integrity, honesty, quality. Read reviews from your neighbors in Chesterbrook, PA to see how we live up to these values every day, in every way.

Local Reviews
for Chesterbrook, PA

DiBiase Heating and Cooling Company Rated 4.8 out of 5 stars based on 4 customer reviews


Great service




Review of DiBiase Heating and Cooling Company

Brian came right on time and performed a tuneup. He is courteous, efficient and knowledgeable. I would recommend.


Top notch outfit




Review of DiBiase Heating and Cooling Company

The Tech was excellent. The service was outstanding. Dibiase has earned my business. They are straight-shooters. As long as they remain so, I will be their customer.


Great service




Review of DiBiase Heating and Cooling Company

Kurt and Mike were great to work with. Their knowledge was evident. They arrived on time and worked efficiently. This is my first experience with this company. I feel good about switching to DiBiase.


Convenient appointment




Review of DiBiase Heating and Cooling Company


Brian B.

Brian B.

Performed heating maintenance, checked air filter ok. Checked voltage, amperage and electrical, measured capacitor. Tested electric back up heaters. Started heat pump, calculated btu output. Tested defrost cycle. Checked operation and temperature rise across coil.

Near Stonehurst Ct, Chesterbrook, PA 19087
Christopher B.

Christopher B.

Performed Heating Tune Up on Amana Heat Pump system. Replaced 20x20x1 Air Filter. Taped along bottom of Filter slot cover due to Air Leakage when testing the system. Reset Filter Alert on Thermostat. Inspected electrical components on Indoor and Outdoor Units. Put system in Heating Mode and measured Refrigerant charge and Air Temperatures. Adjusted temperature and tested Heat Pump and Auxiliary Heat Kit. Measured Amp Draw on Heating Elements and measured air temperature readings. Reviewed Thermostat operation and how to change Filter with homeowner. System operating to manufacturer standards.

Near Stonehurst Ct, Chesterbrook, PA 19087
Brian B.

Brian B.

Performed cooling maintenance, checked media air filter. Checked voltage, amperage and electrical connections, measured capacitor values. Started air conditioner, checked refrigerant charge and temperature drop across coil.

Near Soldiers Square, Chesterbrook, PA 19087
Luis T.

Luis T.

No ac heat pump not coming on, check operation of heat pump, indoor unit runs, but no compressor, found open cap for fan side and open winding on compressor, installed new cap and test operation compressor would not come on, installed super boost and compressor came on, quoted for repairs customer ok repairs, recommend having system replaced

Near Hopkinson Ct, Chesterbrook, PA 19087
Brian B.

Brian B.

Checked condensate leak, checked condensate trap, looks clear, blew out condensate trap. Checked temperature drop, getting only 15 degrees, will need to change refrigerant charge. Due to storm we need to return to further diagnose Returned to continue to diagnose, checked refrigerant charge, found low on charge. Topped off refrigerant charge, balanced by superheat. Checked operation and temperature drop across coil. Recommend replacing vs repairs due to age and r22 refrigerant.

Near Bernard Ct, Chesterbrook, PA 19087
Kurt M.

Kurt M.

Found that duct work at air handler on the the return side is not very good for air flow. Found entire coil sweating except upper left hand side where the air flow does not transfer across very well. Found r410a refrigerant pressures to be 329/148 at 89 degrees. Pressures are pre well on. Only found 14 degree split at indoor unit, but system was keeping 72 degrees inside. He did have refrigerant added within a few weeks ago though explained to him that if the leak is is in the evaporator coil, it could be a $3,000 to $4,000 repair. Recommend he replace the system. He is going to wait at this point until the system stops cooling again.

Near Cheswold Ct, Chesterbrook, PA 19087
Christopher B.

Christopher B.

Returned to site after homeowner called to let us know the squirrel had been caught in the trap. Removed trap to the outside and released the squirrel!!

Near Iroquois Ct, Chesterbrook, PA 19087
Luis T.

Luis T.

Follow up visit for Service, squirrel got into the basement Did not see any animal inside basement door was closed at the time of visit,

Near Iroquois Ct, Chesterbrook, PA 19087
Luis T.

Luis T.

Customer stated ac unit sometimes does not work, check ac operation heat pump with air handler 10 kw back up, down flow position, fitler ok, check temp split only 10 degrees, airflow is set to 800 2 ton heat pump check outdoor unit refrigerant pressures noticed capacitor reading 20 rated at 40, noticed return air is only hitting indoor coil by 50% other 50% is n,Ickes by sheet metal, coils needs a return transition so air passes at 100 % through coil, informed customer about findings system is running customer ok with repairs,,,system running at 72 return 62 supply

Near Cheswold Ct, Chesterbrook, PA 19087
Brian B.

Brian B.

Performed cooling maintenance, checked media air filter. Blew out condensate trap. Checked voltage, amperage and electrical connections, measured capacitor values. Started heat pump, checked refrigerant charge and temperature drop across coil

Near Iroquois Ct, Chesterbrook, PA 19087
Christopher B.

Christopher B.

Service call that the AC was not cooling. Upon arrival spoke with homeowner about issue. System was turned off upon arrival. Inspected indoor coil and found small amounts of ice remaining on coil. Removed ice and put system in operation. Replaced 201 Air Filter provided by the homeowner. Checked Air Measurements and found only a 14 Degree Supply versus return differential. Measured refrigerant charge and found system low on charge. Added 3lbs of 410-A refrigerant to system, charging by Subcooling. Subcooling increased from 1 degree to 10 degrees and temperature split increased to 18 degrees. No dye was added to the system at this time. Would recommend a full AC Tune Maintenance on system.

Near Lafayette Ln, Chesterbrook, PA 19087
Brian B.

Brian B.

Disconnect and remove existing ECM Blower Motor and housing. Install a new OEM Blower Motor Assembly and remount. Wire motor into system. Install new Control Board for Air Handler and wire into system. Set Dipswitch settings on Control Board. Put system in operation and test. Measure Temperature Rise across the Coil.

Near Stonehurst Ct, Chesterbrook, PA 19087
Christopher B.

Christopher B.

Service call that the system was not cooling the home. Upon arrival found indoor temperature at 85 Degrees and the system was set to cooling. Proceeded to the basement to trouble the system. Found indoor Coil and Lineset completely frozen and the blower motor not running. Control board was flashing a 6 Flash Red Light error code indicating an issue with the Blower motor operation. After testing, found blower motor was receiving 244 Volts for the high voltage but was not testing any 24V signal. Blower was attempting to start but would slowly spin a 1/2 rotation and then stop. When system was powered off the Blower wheel would not free spin and had resistance. Recommendation is to replace the ECM Blower Motor. If the Control Board does not send the proper signal to the motor then the Control Board will also need to be replaced. Turned off breakers in the Air Handler and pulled the disconnect for the outdoor unit. We will call Amana in the morning to get pricing and availability for the M

Near Stonehurst Ct, Chesterbrook, PA 19087
Brian B.

Brian B.

Performed cooling maintenance, checked air filter, found clean filter. Blew out condensate trap. Checked voltage, amperage and electrical connections, measured capacitor values, found failed dual run capacitor on outdoor unit. Replaced capacitor. Started air conditioner, checked refrigerant charge and temperature drop across coil.

Near Stonehurst Ct, Chesterbrook, PA 19087
Kurt M.

Kurt M.

Performed precision a/c tune up on Bryant heat pump system. Aprilaire 401 air filter is ok. Checked all electrical conections and components. Found blower motor bearings are going bad causing air handler to shake. Called and got price and availability on motor and wheel. Recommend to homeowner to not put money into repair due to age of heat pump. ( homeowner will let us know) checked refrigerant pressures and temperatures at indoor and outdoor units. Heat pump is working ok at time of service.

Near New Market Ct, Chesterbrook, PA 19087
Brian B.

Brian B.

Performed quality check on heat pump, replaced standard air filter. Checked blower settings. Tested electric back up heaters. Checked voltage, amperage and electrical connections. Started heat pump, measured btu output. Tested defrost cycle. Checked operation and temperature rise across coil.

Near Stonehurst Ct, Chesterbrook, PA 19087
Luis T.

Luis T.

Performed heat pump, check electrical low and high ok replace filter test 15 kw ok check split ok check outdoor test defrost 410 pressures ok installed surge motor protector on blower motor cycle heat pump

Near Iroquois Ct, Chesterbrook, PA 19087
Luis T.

Luis T.

Performed heat pump check up check electrical low and high ok replace air filter, check blower, found blower cap reading 4.5 rated at 7”5 check split ok check outdoor unit 410 pressures ok 280/80 test defrost ok both coils are clean someone else have added refrigerant to system recommend adding dye to system and also replacing blower cap

Near Cavalry Ct, Chesterbrook, PA 19087
Luis T.

Luis T.

Performed peco heat pump inspection check electrical low and high ok filter ok, inspect indoors and outdoor coils ok both are clean, check 15 kw back up ok check splits ok, check refrigerant pressures capacitor and contactor ok test defrost and cycle unit ok

Near Lafayette Ln, Chesterbrook, PA 19087
Luis T.

Luis T.

Performed precision heat tune up on trane gas furnace. Check air filter. Air filter in a healthy climate brand m16 20x25x5. Homeowner to replace. Checked all electrical conections and components. Pulled out burners and found lot of rust and corrosion. ( showed homeowner with camera) checked gas pressure and performed combustion test. Cleaned flame sensor and blew out condensate drain. Recommend replacing gas furnace due to heat exchanger condition. Set up appointment with office.

Near Soldiers Square, Chesterbrook, PA 19087
Christopher B.

Christopher B.

Performed Quality Assurance on Amana Heat Pump system. Completed checklist form in system. Reviewed installation with homeowner and answered any questions.

Near Stonehurst Ct, Chesterbrook, PA 19087
Luis T.

Luis T.

Installed new heat pump and air handler as well as a new whip and disconnect . Set the outdoor on new plastic pad on top of cement pad. New linesets and thermostat were added for the outdoor we triple evacuated the unit after pressure held at 352 psi for ten minutes. We vacuumed down to 134 microns and held for 10 minutes cracked charge and added 13 ounces of r-410 a refrigerant to the system.. we added a new eztrap on the air handler and gravity drained to the side of the house. The new T6 thermostat was added and programmed for operation. System meets factory standards. Thermostat was shown to customer and showed how to operate thermostat. Customer stated check won’t clear til Tuesday call before running the payments so she knows it’s there 20x20x1 air filter

Near Stonehurst Ct, Chesterbrook, PA 19087
Kurt M.

Kurt M.

Performed precision heat tune on American standard heat pump. 20x20x1 air filter is clean. Checked all electrical conections and components. Checked refrigerant pressures and temperatures at indoor and outdoor units. Found temperature rise of only 13 degrees. Went out side and found older r22 heat pump low on charge. Gave homeowner the option of adding refrigerant but do not recommend due to age of heat pump and not knowing how long charge will last. Recommend replacing heat pump system. Set up appointment for Friday between 9- 11am.

Near Stonehurst Ct, Chesterbrook, PA 19087
Zach  C.

Zach C.

Performed peco inspection, checked air filter. Checked voltage, amperage and electrical connections, found blower and dual run capacitor values low. Recommend replacing. Tested electric back up heaters. Started heat pump, checked refrigerant charge, found low on charge. Emailed estimate to replace capacitors and top off charge. Checked operation and temperature drop across coil. Recommend having heat pump serviced regularly.

Near Paddock Dr, Chesterbrook, PA 19087
Brian B.

Brian B.

Performed cooling maintenance checked media air filter ok. Inspected cooling coil. Blew out condensate trap and drain. Tested condensate pump. Checked voltage, amperage and electrical connections, measured capacitor values ok. Started heat pump, checked refrigerant charge and temperature drop across coil. Found no reason for no cooling.