Menu

DiBiase Heating and Cooling Company

Rated 4.9 out of 257 reviews
CALL NOW: 610-873-1244
Your Comfort is Our #1 Priority!

Wayne PA Heating Air Conditioning Service Repair

2018-02-15T17:38:50+00:00

When you need air conditioning, heating and water heater services in Wayne, PA, you need DiBiase Heating & Cooling Company. We’ve earned a reputation over the years for providing customer-first service you can count on.
We live by rock-solid values of integrity, honesty and quality. Read our reviews and find out why your neighbors think of our trusty frog mascot whenever they need local heating, air conditioning and water heater services in Wayne, PA.

Local Reviews
for Wayne, PA

Rated 5.0 out of 5 stars based on 2 customer reviews


Map of Wayne, PA

My AC broke




Our AC broke and we were not able to figure out what happened. I was recommended DiBiase by my general contractor. So I called them. Nicole was pleasant to talk to and explained their process clearly. Their technician Nathan came on time and fixed the issue and was courteous to talk to. We were happy with the results.


Map of Wayne, PA

Punctual, professional and thorough




My wife and I have come to expect complete professionalism and reliability from the DiBiase team. They reach out proactively to schedule seasonal check-ups and show up on time. The technicians are always good people and know what they're doing. Our HVAC system is approaching 20 years old, so we have regular discussions about its limited life expectancy, but they do their best to keep it running as efficiently as possible.


JOSEPH D.

JOSEPH D.

Upon arrival system and pump are running to standards. Complaint that condensate pump is loud and running to much. Nothing wrong with pump. Put isolation pads under pump and installed loop in condensate line to trap water in efforts to make quieter.

Near Poplar Ave, Wayne, PA 19087
Christopher B.

Christopher B.

Performed Precision Air Conditioning Tune Up,on system. Replaced both 16x20x1 Air Filters. Cleaned Condensation Drain Pipe and Pump. Filled and tested operation of Pump. While testing Electrical Components, found Blower Motor Capacitor was measuring below Rating. Installed a new 15 Mfd Capacitor and tested Operation. Measured Refrigerant Charge and temperature splits of system.Thank You for becoming a Service Plan Member for Your Air Conditioning System. We will contact you in the Spring/Summer next year to schedule your next AC Tune Up.

Near Mancill Rd, Wayne, PA 19087
Christopher B.

Christopher B.

Service call that the Boiler was leaking water. Upon arrival, spoke with Homeowner about issue with Boiler. Found the Valve Handle for the Low Water Cutoff had broken off, and the drain on the Low Water Cut Off had a very small drop. Attempted to further close the Valve to stop the leak. Unable to stop the drip, I drained the Boiler down. Need to replace the Valve on the Low Water Cut Off. Will follow up pricing. The whole Low Water Cutoff might have to be replaced, if just the bottom portion with the Valve cannot be replaced on its own.Turned the Power Switch for the Boiler Off. Do Not Operate Boiler until it is filled with water.

Near Poplar Ave, Wayne, PA 19087
Christopher B.

Christopher B.

Service call that the AC was not cooling. Upon arrival, found thermostat turned off and indoor temperature was 83 Degrees. Turned Thermostat on and tested system. Found the Compressor was not Turning on. After troubleshooting, determined the 45/7.5 Mfd Dual Capacitor had failed on the Hermetic Side and was not turning the Compressor on.mInstalled a new Dual Capacitor and put system in operation. Checked Refrigerant Pressures and measured temperature split. Supply Temperature was at 64 Degrees, with a 81 Degree Return Temperature. Checked Air Filters. Due to the inside temperature of 83 Degrees please give the system several hours to properly cool the home.Recommend Service Membership Program which would include an Annual Tune Up on the AC and an Annual Tune Up on the Oil Furnace. Please see attached Estimate.

Near Mancill Rd, Wayne, PA 19087
Christopher B.

Christopher B.

Service call that Package Unit #5 which Supplies the Women’s Locker Room was not working. After troubleshooting system, found that one of the Condenser Fan Motors was seized and not running. This is causing the unit to run in High Head Pressure and elevate all of the Refrigerant readings. Need to replace the Condenser Fan Motor and Test Operation of the system. Can not assess complete performance of the unit without the Condenser Fan Motor in Operation.Called and left a message for Shawn while onsite. Please see attached estimate for pricing of motor.

Near Sugartown Rd, Wayne, PA 19087
Nathan P.

Nathan P.

The following repairs are recommended for the Attic System which supplies the Second and Third Floor.

Near Poplar Ave, Wayne, PA 19087
Nathan P.

Nathan P.

Wet switches tripped due to union webstone connection. Insulated the rest of the supply trunk. System is up to manufacture specifications at this time.

Near Poplar Ave, Wayne, PA 19087
JOSEPH D.

JOSEPH D.

Upon arrival found unit low on charge. Added 2lbs of refrigerant and was told to stop. Unit needed another pound to bring to standards. Low 103 high 360 superheat 10 subcooling 22. Supply45 return 65.Recommend adding dye and another pound.

Near Sugartown Rd, Wayne, PA 19087
Christopher B.

Christopher B.

Performed Precision Air Conditioning Tune Up on the First Floor System. Checked Air Filter. Cleaned EZ Trap Drain Line and Pump. Tested operation of Condensation Pump. Tested Electrical Components on the Indoor and Outdoor Units. Measured Refrigerant Temperatures and Pressures. System is running to standards.Performed Precision Air Conditioning Tune Up on the Second/Third Floor Systems. Checked Air Filter. Cleaned EZ Trap Drain Line and Pump. Tested operation of Pump. Tested Electrical Components on the Indoor and Outdoor Units. Measured Refrigerant Temperatures and Pressures of System. Due to the Air Handler being in the Attic found several areas that we are recommending to be repaired:1.) No Shut Off Switch is present in the Attic at the Air Handler. 2.) The Supply Trunk and Return Box are not wrapped/Insulated. The Supply and Return Box should be insulated due to sweating and condensation that form on the outside. 3.) Seal all Ductwork. Their are gaps in the Duct Work and th

Near Poplar Ave, Wayne, PA 19087
Nathan P.

Nathan P.

We will disconnect, remove, and dispose of the existing vent piping. We will install new stainless steel vent piping from the boiler to the outside wall. We will seal the hole at the outside wall with watertight cement. We will high temp silicone all of the joints as required.We will install a new Honeywell intermittent pilot module for the boiler. We will test the boiler operaiton.We will clean and service the boiler in accordance with our maintenance plan. This service includes cleaning burners, cleaning sensors, cleaning pilot gas line and orifice, cleaning pressure switch tubing line and monitoring pressure, inspection of heat exchanger, combustion analysis and efficiency test will be performed.Made boiler repairs as stated above and tested operation.

Near Gulph Hills Rd, Wayne, PA 19087
Nathan P.

Nathan P.

Performed precision heat tune up. Found circulator leaking and water feeder not feeding. Both need replaced.

Near Gulph Hills Rd, Wayne, PA 19087
JOSEPH D.

JOSEPH D.

Found unit on rooftop locked out on fault code for rollout switch. Located rollout and reset and unit attempted to restart. Unit then went into fault code 7 indicating the Evap sensor was open. Bypassed sensor and unit was still going into lockout. Moved wires around on board and unit restarted and stayed running. Contactor making excessive noise.Need to replace control board for compressor, contactor, and evaporator temperature sensor that was mounted to suction line.

Near Sugartown Rd, Wayne, PA 19087
Christopher B.

Christopher B.

Performed Precision Air Conditioning Tune Up on system. Replaced 16x25x1 Air Filter. Cleaned Condensation Drain Pipe and Pump. Tested Operation of Pump. Inspected Indoor Coil. Coil is poor due to rust. Transformer on Furnace is making a buzzing noise. This is an indication that it could be failing. Found Contactor on Outdoor Unit is very worn and pitted. If the Contactor fails, the Outdoor Unit will not operate. Recommend replacement of the Contactor and Transformer. Tested Refrigerant Levels of system. System is operational, but the Refrigeration Cycle is running very inefficiently. During high Heat/Load days the system may struggle to maintain temperature within the home. Due to overall condition of the Furnave/AC and age, recommend replacement of system.

Near Wembley Dr, Wayne, PA 19087
Nathan P.

Nathan P.

Just repaired and old GE AC in Devon to keep it going through the season

Near Chester Valley Trail, Wayne, PA 19087
Nathan P.

Nathan P.

33yr AC unit with a bad condenser fan in Wayne

Near Thomas Rd, Wayne, PA 19087
Bryan D.

Bryan D.

Performing an Ac tune up in malvern

Near Wembley Dr, Wayne, PA 19087
Bryan D.

Bryan D.

Performing an Ac tune up in malvern

Near Wembley Dr, Wayne, PA 19087
Bryan D.

Bryan D.

Working on a leaking Carrier air conditioner in Wayne.

Near Dresher Way, Wayne, PA 19087
Bryan D.

Bryan D.

Working on a leaking Carrier air conditioner in Wayne.

Near Dresher Way, Wayne, PA 19087
Bryan D.

Bryan D.

Heat Call issue in Wayne on an American Standard Gas Furnace. Found Thermostat was faulty and not shutting the Furnace off. Also performed a Heat Tune Up after replacing the Thermostat.

Near Valley Forge Rd, Wayne, PA 19087
Bryan D.

Bryan D.

Heat Call issue in Wayne on an American Standard Gas Furnace. Found Thermostat was faulty and not shutting the Furnace off. Also performed a Heat Tune Up after replacing the Thermostat.

Near Valley Forge Rd, Wayne, PA 19087

DiBiase HVAC