610-873-1244 Book Online Text Us

West Brandywine Township, PA

Expert HVAC Service and More in West Brandywine Township, PA

DiBiase Heating and Cooling Company provides a full range of services to keep your home comfortable and efficient year-round in West Brandywine Township, PA. Whether you need HVAC repair, installation, or maintenance, we’ve got you covered. Our team also specializes in improving indoor air quality with air purifiers, humidifiers, and ductwork services. Looking for water heater solutions? We offer repairs and replacements for both tank and tankless systems. Additionally, our energy services, including air sealing, insulation, and energy audits, help homeowners save on utility costs while maximizing comfort. Whatever your home’s needs, DiBiase Heating and Cooling Company is here to deliver expert service.

Founded in 2008, DiBiase Heating and Cooling Company is a family-owned and operated company that’s committed to delivering honest, reliable service. We take pride in our expertise, offering certified technicians who provide top-quality HVAC, plumbing, and energy services. What sets us apart is our focus on process and integrity—we do the job right the first time, ensuring your home is always in good hands. Ready to experience the DiBiase difference? Call 610-873-1244 or contact us online today to schedule your service!

Recent Jobs and Reviews in West Brandywine Township, PA

Rated 4.5 out of 5 stars based on 8 customer reviews

Customers say: The overall sentiment across these reviews is overwhelmingly positive, reflecting high levels of customer satisfaction and appreciation. Customers consistently express enthusiasm about the professionalism, efficiency, and expertise demonstrated by the service technicians. Recurring themes include praise for the friendly and courteous demeanor of staff members, with many reviewers highlighting how technicians take time to provide thorough explanations and patiently answer questions. The company's responsiveness stands out as a significant strength, with customers noting quick service, timely arrivals, and even after-hours and weekend availability during urgent situations. Technical competence is frequently celebrated, with reviewers expressing confidence in the quality of work performed and trust in the recommendations provided. Many customers specifically mention feeling valued and respected, noting that technicians are considerate of their property and demonstrate genuine care in their interactions. The positive experiences have fostered strong loyalty, with some customers indicating they have switched to this company from previous providers or expressing intent to request specific technicians for future visits. The tone throughout is one of gratitude and recommendation, with customers frequently using words like "excellent," "wonderful," "great," and "highly recommend" to convey their satisfaction with both the technical service and interpersonal experience.

Our Local Reviews by City

Job Locations and Reviews

Completed AC tune up for 3 Ton Bosch inverter system

Replaced 18x30x1 filter
Indoor and outdoor coils in good condition 
Inspected wiring, controls, electric motors and components; equipment has surge protection 
Measured temperature split and static pressure 
Inspected drains; cleared EZ trap, added treatment tabs to drain pan. 
Checked integrity of compressor motor 

Assessed refrigerant charge checked pressures. 10° SC in force test mode and at 57Hz Good

Homeowner mentioned that the house is unbalanced one bedroom remains warm “muggy”. There are (9) supply runs (5) 8” (3) 7” (1) 6” I believe. 16” Return 18x30x1 ceiling grille. There are no dampers on the supply take offs. The ductwork and attic insulation would need to be evaluated as well. Offered and left estimate for Honeywell S1200 with room sensor can place the room sensor wherever. Can be used to control cooling from wherever you place sensors. Additional room sensors can be added in future. 

AC system operating well at thi
Completed AC tune up for 3 Ton Bosch inverter system

Replaced 18x30x1 filter
Indoor and outdoor coils in good condition 
Inspected wiring, controls, electric motors and components; equipment has surge protection 
Measured temperature split and static pressure 
Inspected drains; cleared EZ trap, added treatment tabs to drain pan. 
Checked integrity of compressor motor 

Assessed refrigerant charge checked pressures. 10° SC in force test mode and at 57Hz Good

Homeowner mentioned that the house is unbalanced one bedroom remains warm “muggy”. There are (9) supply runs (5) 8” (3) 7” (1) 6” I believe. 16” Return 18x30x1 ceiling grille. There are no dampers on the supply take offs. The ductwork and attic insulation would need to be evaluated as well. Offered and left estimate for Honeywell S1200 with room sensor can place the room sensor wherever. Can be used to control cooling from wherever you place sensors. Additional room sensors can be added in future. 

AC system operating well at thi
Barry P.
Barry P. Checked in
Completed AC tune up for 3 Ton Bosch inverter system Replaced 18x30x1 filter Indoor and outdoor coils in good condition Inspected wiring, controls, electric motors and components; equipment has surge protection Measured temperature split and static pressure Inspected drains; cleared EZ trap, added treatment tabs to drain pan. Checked integrity of compressor motor Assessed refrigerant charge checked pressures. 10° SC in force test mode and at 57Hz Good Homeowner mentioned that the house is unbalanced one bedroom remains warm “muggy”. There are (9) supply runs (5) 8” (3) 7” (1) 6” I believe. 16” Return 18x30x1 ceiling grille. There are no dampers on the supply take offs. The ductwork and attic insulation would need to be evaluated as well. Offered and left estimate for Honeywell S1200 with room sensor can place the room sensor wherever. Can be used to control cooling from wherever you place sensors. Additional room sensors can be added in future. AC system operating well at thi
West Brandywine Township, PA 19320
Review
Luis is friendly, helpful and knowledgeable.9
Robert - West Brandywine Township, PA 19320
Luis 5-13-26 
Performed ac tune up on Bosch 3 ton heat pump system, check, indoor coils, flush drain test condensate pump inspect blower motor check air filter ok. Check supply and return air temps. Check outdoor unit coils and electrical refrigerant levels ok. Cycle heat pump ok. System is working properly at the time of service. During today’s visit I wired humidifier to thermostat, now is connected to u1 on EMI and thermostat.
Luis 5-13-26 
Performed ac tune up on Bosch 3 ton heat pump system, check, indoor coils, flush drain test condensate pump inspect blower motor check air filter ok. Check supply and return air temps. Check outdoor unit coils and electrical refrigerant levels ok. Cycle heat pump ok. System is working properly at the time of service. During today’s visit I wired humidifier to thermostat, now is connected to u1 on EMI and thermostat.
Luis T.
Luis T. Checked in
Luis 5-13-26 Performed ac tune up on Bosch 3 ton heat pump system, check, indoor coils, flush drain test condensate pump inspect blower motor check air filter ok. Check supply and return air temps. Check outdoor unit coils and electrical refrigerant levels ok. Cycle heat pump ok. System is working properly at the time of service. During today’s visit I wired humidifier to thermostat, now is connected to u1 on EMI and thermostat.
West Brandywine Township, PA 19320
I arrived for a no Cooling call on a Maytag 10 yr old system. Blank thermostat due to the water safety tripped. I started with inspecting the indoor unit. I checked the filter and it was dirty , but replaced on site (supplied by the customer) . I made sure the blower motor runs , and that the indoor coil was free of ice or debri. I did remove some water from the pan . I reset the switch and I went to the outdoor unit . I hooked up my gauges and found the system was very low on charge had a 42° super heat and 2° sub cool . I talked everything over with the customers and we all agreed to have a estimate scheduled for pricing on new AC equipment. They are scheduled for Sunday at noon. I collected for $149 for diagnostics for today paid by credit card.
I arrived for a no Cooling call on a Maytag 10 yr old system. Blank thermostat due to the water safety tripped. I started with inspecting the indoor unit. I checked the filter and it was dirty , but replaced on site (supplied by the customer) . I made sure the blower motor runs , and that the indoor coil was free of ice or debri. I did remove some water from the pan . I reset the switch and I went to the outdoor unit . I hooked up my gauges and found the system was very low on charge had a 42° super heat and 2° sub cool . I talked everything over with the customers and we all agreed to have a estimate scheduled for pricing on new AC equipment. They are scheduled for Sunday at noon. I collected for $149 for diagnostics for today paid by credit card.
Daniel R.
Daniel R. Checked in
I arrived for a no Cooling call on a Maytag 10 yr old system. Blank thermostat due to the water safety tripped. I started with inspecting the indoor unit. I checked the filter and it was dirty , but replaced on site (supplied by the customer) . I made sure the blower motor runs , and that the indoor coil was free of ice or debri. I did remove some water from the pan . I reset the switch and I went to the outdoor unit . I hooked up my gauges and found the system was very low on charge had a 42° super heat and 2° sub cool . I talked everything over with the customers and we all agreed to have a estimate scheduled for pricing on new AC equipment. They are scheduled for Sunday at noon. I collected for $149 for diagnostics for today paid by credit card.
West Brandywine Township, PA 19320
Diilon M.
Diilon M. Checked in
Est
West Brandywine Township, PA 19320
Luis 2-19-26 customer has oil boiler, summer winter set up, has mixing valve. Customer states he does not hit water during cold temperatures. I check aqua start settings, 200/160 oil boiler is around 19 years old. I provided estimate to install electric water heater, there is a 230 volt wire that used to be hot water back before replacing oil boiler, 30 amp breaker, we will need 60 amp disconnect and run wire to new location of waste heater, (next to boiler), I would also recommend getting an estimate to replace boiler, (boiler block is leaking). Home comfort consultant to come out tomorrow at 10 am.
Luis 2-19-26 customer has oil boiler, summer winter set up, has mixing valve. Customer states he does not hit water during cold temperatures. I check aqua start settings, 200/160 oil boiler is around 19 years old. I provided estimate to install electric water heater, there is a 230 volt wire that used to be hot water back before replacing oil boiler, 30 amp breaker, we will need 60 amp disconnect and run wire to new location of waste heater, (next to boiler), I would also recommend getting an estimate to replace boiler, (boiler block is leaking). Home comfort consultant to come out tomorrow at 10 am.
Luis T.
Luis T. Checked in
Luis 2-19-26 customer has oil boiler, summer winter set up, has mixing valve. Customer states he does not hit water during cold temperatures. I check aqua start settings, 200/160 oil boiler is around 19 years old. I provided estimate to install electric water heater, there is a 230 volt wire that used to be hot water back before replacing oil boiler, 30 amp breaker, we will need 60 amp disconnect and run wire to new location of waste heater, (next to boiler), I would also recommend getting an estimate to replace boiler, (boiler block is leaking). Home comfort consultant to come out tomorrow at 10 am.
West Brandywine Township, PA 19320
Luis 2-16-26 performed heat pump inspection on 2020 Bosch inverter system, (air handler does not have any back up heat) they use electric baseboard as back up heat. Check all electrical connections and components, inspect air filter. I left new filter for customer to replace it soon. I check airflow and temperature rise ok 87/64 check outdoor heat pump check all electrical and refrigeration numbers from inverter board. Test defrost ok. As unit goes into defrost cold air is coming from air vents. System is running properly at the time of service.
Luis 2-16-26 performed heat pump inspection on 2020 Bosch inverter system, (air handler does not have any back up heat) they use electric baseboard as back up heat. Check all electrical connections and components, inspect air filter. I left new filter for customer to replace it soon. I check airflow and temperature rise ok 87/64 check outdoor heat pump check all electrical and refrigeration numbers from inverter board. Test defrost ok. As unit goes into defrost cold air is coming from air vents. System is running properly at the time of service.
Luis T.
Luis T. Checked in
Luis 2-16-26 performed heat pump inspection on 2020 Bosch inverter system, (air handler does not have any back up heat) they use electric baseboard as back up heat. Check all electrical connections and components, inspect air filter. I left new filter for customer to replace it soon. I check airflow and temperature rise ok 87/64 check outdoor heat pump check all electrical and refrigeration numbers from inverter board. Test defrost ok. As unit goes into defrost cold air is coming from air vents. System is running properly at the time of service.
West Brandywine Township, PA 19320
I arrived for a heat pump not keeping up with temperature. I started downstairs at the air handler. I had a 64 return and a 92 supply heat pump was running only but auxiliary was not running. I opened up the air handler. The board had a (E0) code. Which is a EEPROM malfunction. I checked all my connections and reset the system for 10 min . I turned the system on and the thermostat read heat 2 which is the auxiliary heat kicking in with the heat pump now my temperature went from 92° supply to 119° system is back up and running again. I did put a call into carrier for them to call me back . so I collected for my time and diagnosis for today.
I arrived for a heat pump not keeping up with temperature. I started downstairs at the air handler. I had a 64 return and a 92 supply heat pump was running only but auxiliary was not running. I opened up the air handler. The board had a (E0) code. Which is a EEPROM malfunction. I checked all my connections and reset the system for 10 min . I turned the system on and the thermostat read heat 2 which is the auxiliary heat kicking in with the heat pump now my temperature went from 92° supply to 119° system is back up and running again. I did put a call into carrier for them to call me back . so I collected for my time and diagnosis for today.
Daniel R.
Daniel R. Checked in
I arrived for a heat pump not keeping up with temperature. I started downstairs at the air handler. I had a 64 return and a 92 supply heat pump was running only but auxiliary was not running. I opened up the air handler. The board had a (E0) code. Which is a EEPROM malfunction. I checked all my connections and reset the system for 10 min . I turned the system on and the thermostat read heat 2 which is the auxiliary heat kicking in with the heat pump now my temperature went from 92° supply to 119° system is back up and running again. I did put a call into carrier for them to call me back . so I collected for my time and diagnosis for today.
West Brandywine Township, PA 19320
Replaced 70/7.5 uF dual capacitor at outdoor unit.
Origin capacitor was very weak. Reading 28uF.
Afterwards tested system.
Measured amp draw of start winding to capacitor 8.6A Good.

Measured temperature rise @ air handler. 66-86=20° Good
Outdoor dry bulb temperature 16°F

System operating well at this time.
Collected balance
Replaced 70/7.5 uF dual capacitor at outdoor unit.
Origin capacitor was very weak. Reading 28uF.
Afterwards tested system.
Measured amp draw of start winding to capacitor 8.6A Good.

Measured temperature rise @ air handler. 66-86=20° Good
Outdoor dry bulb temperature 16°F

System operating well at this time.
Collected balance
Barry P.
Barry P. Checked in
Replaced 70/7.5 uF dual capacitor at outdoor unit. Origin capacitor was very weak. Reading 28uF. Afterwards tested system. Measured amp draw of start winding to capacitor 8.6A Good. Measured temperature rise @ air handler. 66-86=20° Good Outdoor dry bulb temperature 16°F System operating well at this time. Collected balance
West Brandywine Township, PA 19320
I arrived for a thermostat not working.  I found condensation pump was running nonstop. I traced out my 3/8 tubing and it ran outside with the line set. It had about 6 foot a line outside the wall, it was frozen, I cut the line out, sealed up the access. Then I rerouted the 3/8 tubing to the basement sink and used PVC to guide water into the sink for  the 3/8 tubing. No charge . The system is back up and running.
I arrived for a thermostat not working.  I found condensation pump was running nonstop. I traced out my 3/8 tubing and it ran outside with the line set. It had about 6 foot a line outside the wall, it was frozen, I cut the line out, sealed up the access. Then I rerouted the 3/8 tubing to the basement sink and used PVC to guide water into the sink for  the 3/8 tubing. No charge . The system is back up and running.
Daniel R.
Daniel R. Checked in
I arrived for a thermostat not working. I found condensation pump was running nonstop. I traced out my 3/8 tubing and it ran outside with the line set. It had about 6 foot a line outside the wall, it was frozen, I cut the line out, sealed up the access. Then I rerouted the 3/8 tubing to the basement sink and used PVC to guide water into the sink for the 3/8 tubing. No charge . The system is back up and running.
West Brandywine Township, PA 19320
Neighbor came over and told me she can smell oil. Duplex house. She lives on the other side. Robert doesn’t come down to basement often 

Found copious oil in equipment pan, blower compartment and filter rack.
Cleaned as much as possible and left paper towels to absorb oil that is under furnace where I cannot get to it.
Replaced failed wet switch.
Used (2) burner gaskets folded in half and placed under bottom half of burner so that burner is pitched in such a way that oil will spray into combustion chamber. Changed post purge time from 0:00 to 1 min.

Completed oil Heat tune up.
Replaced Aprilaire 413 filter. 
Heat exchanger and flues are clean.
Replaced RF1 oil filter, replaced .60 80A nozzle and arranged electrodes.
Combustion smoke and draft test: Pass

Set new humidifier to 35%. Pad is new. Tested operations and water leaks. 

We will have to make a return visit to pick up the towels that are used to wick up any oil left in pan and assess the oil leak situation further.
After my fi
Neighbor came over and told me she can smell oil. Duplex house. She lives on the other side. Robert doesn’t come down to basement often 

Found copious oil in equipment pan, blower compartment and filter rack.
Cleaned as much as possible and left paper towels to absorb oil that is under furnace where I cannot get to it.
Replaced failed wet switch.
Used (2) burner gaskets folded in half and placed under bottom half of burner so that burner is pitched in such a way that oil will spray into combustion chamber. Changed post purge time from 0:00 to 1 min.

Completed oil Heat tune up.
Replaced Aprilaire 413 filter. 
Heat exchanger and flues are clean.
Replaced RF1 oil filter, replaced .60 80A nozzle and arranged electrodes.
Combustion smoke and draft test: Pass

Set new humidifier to 35%. Pad is new. Tested operations and water leaks. 

We will have to make a return visit to pick up the towels that are used to wick up any oil left in pan and assess the oil leak situation further.
After my fi
Barry P.
Barry P. Checked in
Neighbor came over and told me she can smell oil. Duplex house. She lives on the other side. Robert doesn’t come down to basement often Found copious oil in equipment pan, blower compartment and filter rack. Cleaned as much as possible and left paper towels to absorb oil that is under furnace where I cannot get to it. Replaced failed wet switch. Used (2) burner gaskets folded in half and placed under bottom half of burner so that burner is pitched in such a way that oil will spray into combustion chamber. Changed post purge time from 0:00 to 1 min. Completed oil Heat tune up. Replaced Aprilaire 413 filter. Heat exchanger and flues are clean. Replaced RF1 oil filter, replaced .60 80A nozzle and arranged electrodes. Combustion smoke and draft test: Pass Set new humidifier to 35%. Pad is new. Tested operations and water leaks. We will have to make a return visit to pick up the towels that are used to wick up any oil left in pan and assess the oil leak situation further. After my fi
West Brandywine Township, PA 19320
Review
Boyd Benjamin - West Brandywine Township, PA 19320
Response from DiBiase Heating and Cooling Company:

Hi Boyd! Thank you so much for leaving us a 5-star review!

Review
Explained things well
Robert - West Brandywine Township, PA 19320
Response from DiBiase Heating and Cooling Company:

We are so glad to hear that you had a good experience.

Review
Did not help
Robert - West Brandywine Township, PA 19320
Review
Employee was polite and courteous
Robert - West Brandywine Township, PA 19320
Review
Great job as always.
Phil - West Brandywine Township, PA 19320
Review
Very responsive, tech fixed the problem and explained the path forward. Very professional, did a great job. I’m not happy with the furnace at all, as it has required service multiple times since it was installed.
Jack - West Brandywine Township, PA 19320
Review
Kurt was professional, timely, & friendly.100% satisfactory experience.
Marie - West Brandywine Township, PA 19320
Review
List did a great job as always.
Phil - West Brandywine Township, PA 19320
Request Service
servicedetailscustomerreturningschedule
*
Details Regarding Your Request...
Optional: Drag and drop photos and/or videos:
Max. file size: 4 MB.
Your Contact and Service Location...
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
*
What Is Convenient For You?
*
What time of day is best for you?
First Available
Morning
Afternoon
*

Call For Same Day Service/Emergencies at 610-873-1244 .

By pressing Submit I agree to receive phone, email, or text messages from DiBiase Heating and Cooling Company to the provided mobile number and also agree to the DiBiase Heating and Cooling Company terms and privacy policy. Message & data rates may apply. Consent is not a condition of purchase. We will never share your personal information with third parties for marketing purposes.
Back Next