610-873-1244 Book Online Text Us

West Brandywine Township, PA

Expert HVAC Service and More in West Brandywine Township, PA

DiBiase Heating and Cooling Company provides a full range of services to keep your home comfortable and efficient year-round in West Brandywine Township, PA. Whether you need HVAC repair, installation, or maintenance, we’ve got you covered. Our team also specializes in improving indoor air quality with air purifiers, humidifiers, and ductwork services. Looking for water heater solutions? We offer repairs and replacements for both tank and tankless systems. Additionally, our energy services, including air sealing, insulation, and energy audits, help homeowners save on utility costs while maximizing comfort. Whatever your home’s needs, DiBiase Heating and Cooling Company is here to deliver expert service.

Founded in 2008, DiBiase Heating and Cooling Company is a family-owned and operated company that’s committed to delivering honest, reliable service. We take pride in our expertise, offering certified technicians who provide top-quality HVAC, plumbing, and energy services. What sets us apart is our focus on process and integrity—we do the job right the first time, ensuring your home is always in good hands. Ready to experience the DiBiase difference? Call 610-873-1244 or contact us online today to schedule your service!

Recent Jobs and Reviews in West Brandywine Township, PA

Rated 4.4 out of 5 stars based on 7 customer reviews

Customers say: The reviews reflect an overwhelmingly positive sentiment toward the service technicians and their work. Customers consistently express appreciation for the technicians' professionalism, knowledge, and communication skills. A recurring theme is the thoroughness of the service provided, with many reviewers highlighting how technicians took time to explain technical issues in understandable terms. Customers frequently mention the technicians' ability to diagnose and solve problems efficiently, even in challenging situations. The reviews convey satisfaction with the quality of work performed, timely service, and helpful recommendations for system maintenance and improvement. The overall tone is decidedly positive, with customers expressing gratitude for having their heating and cooling systems restored to proper functioning, particularly during critical times. Many reviews indicate an intention to request the same technicians for future service needs, demonstrating a high level of trust and satisfaction with the service experience.

Our Local Reviews by City

Job Locations and Reviews

Diilon M.
Diilon M. Checked in
Est
West Brandywine Township, PA 19320
Luis 2-19-26 customer has oil boiler, summer winter set up, has mixing valve. Customer states he does not hit water during cold temperatures. I check aqua start settings, 200/160 oil boiler is around 19 years old. I provided estimate to install electric water heater, there is a 230 volt wire that used to be hot water back before replacing oil boiler, 30 amp breaker, we will need 60 amp disconnect and run wire to new location of waste heater, (next to boiler), I would also recommend getting an estimate to replace boiler, (boiler block is leaking). Home comfort consultant to come out tomorrow at 10 am.
Luis 2-19-26 customer has oil boiler, summer winter set up, has mixing valve. Customer states he does not hit water during cold temperatures. I check aqua start settings, 200/160 oil boiler is around 19 years old. I provided estimate to install electric water heater, there is a 230 volt wire that used to be hot water back before replacing oil boiler, 30 amp breaker, we will need 60 amp disconnect and run wire to new location of waste heater, (next to boiler), I would also recommend getting an estimate to replace boiler, (boiler block is leaking). Home comfort consultant to come out tomorrow at 10 am.
Luis T.
Luis T. Checked in
Luis 2-19-26 customer has oil boiler, summer winter set up, has mixing valve. Customer states he does not hit water during cold temperatures. I check aqua start settings, 200/160 oil boiler is around 19 years old. I provided estimate to install electric water heater, there is a 230 volt wire that used to be hot water back before replacing oil boiler, 30 amp breaker, we will need 60 amp disconnect and run wire to new location of waste heater, (next to boiler), I would also recommend getting an estimate to replace boiler, (boiler block is leaking). Home comfort consultant to come out tomorrow at 10 am.
West Brandywine Township, PA 19320
Luis 2-16-26 performed heat pump inspection on 2020 Bosch inverter system, (air handler does not have any back up heat) they use electric baseboard as back up heat. Check all electrical connections and components, inspect air filter. I left new filter for customer to replace it soon. I check airflow and temperature rise ok 87/64 check outdoor heat pump check all electrical and refrigeration numbers from inverter board. Test defrost ok. As unit goes into defrost cold air is coming from air vents. System is running properly at the time of service.
Luis 2-16-26 performed heat pump inspection on 2020 Bosch inverter system, (air handler does not have any back up heat) they use electric baseboard as back up heat. Check all electrical connections and components, inspect air filter. I left new filter for customer to replace it soon. I check airflow and temperature rise ok 87/64 check outdoor heat pump check all electrical and refrigeration numbers from inverter board. Test defrost ok. As unit goes into defrost cold air is coming from air vents. System is running properly at the time of service.
Luis T.
Luis T. Checked in
Luis 2-16-26 performed heat pump inspection on 2020 Bosch inverter system, (air handler does not have any back up heat) they use electric baseboard as back up heat. Check all electrical connections and components, inspect air filter. I left new filter for customer to replace it soon. I check airflow and temperature rise ok 87/64 check outdoor heat pump check all electrical and refrigeration numbers from inverter board. Test defrost ok. As unit goes into defrost cold air is coming from air vents. System is running properly at the time of service.
West Brandywine Township, PA 19320
I arrived for a heat pump not keeping up with temperature. I started downstairs at the air handler. I had a 64 return and a 92 supply heat pump was running only but auxiliary was not running. I opened up the air handler. The board had a (E0) code. Which is a EEPROM malfunction. I checked all my connections and reset the system for 10 min . I turned the system on and the thermostat read heat 2 which is the auxiliary heat kicking in with the heat pump now my temperature went from 92° supply to 119° system is back up and running again. I did put a call into carrier for them to call me back . so I collected for my time and diagnosis for today.
I arrived for a heat pump not keeping up with temperature. I started downstairs at the air handler. I had a 64 return and a 92 supply heat pump was running only but auxiliary was not running. I opened up the air handler. The board had a (E0) code. Which is a EEPROM malfunction. I checked all my connections and reset the system for 10 min . I turned the system on and the thermostat read heat 2 which is the auxiliary heat kicking in with the heat pump now my temperature went from 92° supply to 119° system is back up and running again. I did put a call into carrier for them to call me back . so I collected for my time and diagnosis for today.
Daniel R.
Daniel R. Checked in
I arrived for a heat pump not keeping up with temperature. I started downstairs at the air handler. I had a 64 return and a 92 supply heat pump was running only but auxiliary was not running. I opened up the air handler. The board had a (E0) code. Which is a EEPROM malfunction. I checked all my connections and reset the system for 10 min . I turned the system on and the thermostat read heat 2 which is the auxiliary heat kicking in with the heat pump now my temperature went from 92° supply to 119° system is back up and running again. I did put a call into carrier for them to call me back . so I collected for my time and diagnosis for today.
West Brandywine Township, PA 19320
Replaced 70/7.5 uF dual capacitor at outdoor unit.
Origin capacitor was very weak. Reading 28uF.
Afterwards tested system.
Measured amp draw of start winding to capacitor 8.6A Good.

Measured temperature rise @ air handler. 66-86=20° Good
Outdoor dry bulb temperature 16°F

System operating well at this time.
Collected balance
Replaced 70/7.5 uF dual capacitor at outdoor unit.
Origin capacitor was very weak. Reading 28uF.
Afterwards tested system.
Measured amp draw of start winding to capacitor 8.6A Good.

Measured temperature rise @ air handler. 66-86=20° Good
Outdoor dry bulb temperature 16°F

System operating well at this time.
Collected balance
Barry P.
Barry P. Checked in
Replaced 70/7.5 uF dual capacitor at outdoor unit. Origin capacitor was very weak. Reading 28uF. Afterwards tested system. Measured amp draw of start winding to capacitor 8.6A Good. Measured temperature rise @ air handler. 66-86=20° Good Outdoor dry bulb temperature 16°F System operating well at this time. Collected balance
West Brandywine Township, PA 19320
I arrived for a thermostat not working.  I found condensation pump was running nonstop. I traced out my 3/8 tubing and it ran outside with the line set. It had about 6 foot a line outside the wall, it was frozen, I cut the line out, sealed up the access. Then I rerouted the 3/8 tubing to the basement sink and used PVC to guide water into the sink for  the 3/8 tubing. No charge . The system is back up and running.
I arrived for a thermostat not working.  I found condensation pump was running nonstop. I traced out my 3/8 tubing and it ran outside with the line set. It had about 6 foot a line outside the wall, it was frozen, I cut the line out, sealed up the access. Then I rerouted the 3/8 tubing to the basement sink and used PVC to guide water into the sink for  the 3/8 tubing. No charge . The system is back up and running.
Daniel R.
Daniel R. Checked in
I arrived for a thermostat not working. I found condensation pump was running nonstop. I traced out my 3/8 tubing and it ran outside with the line set. It had about 6 foot a line outside the wall, it was frozen, I cut the line out, sealed up the access. Then I rerouted the 3/8 tubing to the basement sink and used PVC to guide water into the sink for the 3/8 tubing. No charge . The system is back up and running.
West Brandywine Township, PA 19320
Neighbor came over and told me she can smell oil. Duplex house. She lives on the other side. Robert doesn’t come down to basement often 

Found copious oil in equipment pan, blower compartment and filter rack.
Cleaned as much as possible and left paper towels to absorb oil that is under furnace where I cannot get to it.
Replaced failed wet switch.
Used (2) burner gaskets folded in half and placed under bottom half of burner so that burner is pitched in such a way that oil will spray into combustion chamber. Changed post purge time from 0:00 to 1 min.

Completed oil Heat tune up.
Replaced Aprilaire 413 filter. 
Heat exchanger and flues are clean.
Replaced RF1 oil filter, replaced .60 80A nozzle and arranged electrodes.
Combustion smoke and draft test: Pass

Set new humidifier to 35%. Pad is new. Tested operations and water leaks. 

We will have to make a return visit to pick up the towels that are used to wick up any oil left in pan and assess the oil leak situation further.
After my fi
Neighbor came over and told me she can smell oil. Duplex house. She lives on the other side. Robert doesn’t come down to basement often 

Found copious oil in equipment pan, blower compartment and filter rack.
Cleaned as much as possible and left paper towels to absorb oil that is under furnace where I cannot get to it.
Replaced failed wet switch.
Used (2) burner gaskets folded in half and placed under bottom half of burner so that burner is pitched in such a way that oil will spray into combustion chamber. Changed post purge time from 0:00 to 1 min.

Completed oil Heat tune up.
Replaced Aprilaire 413 filter. 
Heat exchanger and flues are clean.
Replaced RF1 oil filter, replaced .60 80A nozzle and arranged electrodes.
Combustion smoke and draft test: Pass

Set new humidifier to 35%. Pad is new. Tested operations and water leaks. 

We will have to make a return visit to pick up the towels that are used to wick up any oil left in pan and assess the oil leak situation further.
After my fi
Barry P.
Barry P. Checked in
Neighbor came over and told me she can smell oil. Duplex house. She lives on the other side. Robert doesn’t come down to basement often Found copious oil in equipment pan, blower compartment and filter rack. Cleaned as much as possible and left paper towels to absorb oil that is under furnace where I cannot get to it. Replaced failed wet switch. Used (2) burner gaskets folded in half and placed under bottom half of burner so that burner is pitched in such a way that oil will spray into combustion chamber. Changed post purge time from 0:00 to 1 min. Completed oil Heat tune up. Replaced Aprilaire 413 filter. Heat exchanger and flues are clean. Replaced RF1 oil filter, replaced .60 80A nozzle and arranged electrodes. Combustion smoke and draft test: Pass Set new humidifier to 35%. Pad is new. Tested operations and water leaks. We will have to make a return visit to pick up the towels that are used to wick up any oil left in pan and assess the oil leak situation further. After my fi
West Brandywine Township, PA 19320
Luis 1-9-26 perform heat tuneup on a one year-old trane fully communicating heat pump system. Went to the indoor air handler and outside heat pump check checked refrigerant charge through thermostat no error it’s showing. I also tested 10 KW back up heat ok. Replacement of 413 filter. Refrigerant levels and Oreos. I corrected low voltage wiring on outside and used different anchor for thermostat base. Cycle heat pump ok. We also lock out electric heat at 35° per customer request.
Luis 1-9-26 perform heat tuneup on a one year-old trane fully communicating heat pump system. Went to the indoor air handler and outside heat pump check checked refrigerant charge through thermostat no error it’s showing. I also tested 10 KW back up heat ok. Replacement of 413 filter. Refrigerant levels and Oreos. I corrected low voltage wiring on outside and used different anchor for thermostat base. Cycle heat pump ok. We also lock out electric heat at 35° per customer request.
Luis T.
Luis T. Checked in
Luis 1-9-26 perform heat tuneup on a one year-old trane fully communicating heat pump system. Went to the indoor air handler and outside heat pump check checked refrigerant charge through thermostat no error it’s showing. I also tested 10 KW back up heat ok. Replacement of 413 filter. Refrigerant levels and Oreos. I corrected low voltage wiring on outside and used different anchor for thermostat base. Cycle heat pump ok. We also lock out electric heat at 35° per customer request.
West Brandywine Township, PA 19320
Kurt M.
Kurt M. Checked in
Performed precision a/c tune up on amana a/c system. Replaced 18x24x1 filter. Checked all electrical connections and components. Cleaned ez trap. Checked temperature split. Found no surge protection on Ecm blower motor, provided estimate. Also found dirty outside coil, provided estimate to clean outside coil. Checked refrigerant pressures and temperatures at indoor and outdoor units. A/c is working properly at time of service.
West Brandywine Township, PA 19320
wolferaaron868@gmail.com
wolferaaron868@gmail.com Checked in
Upon arrival, I performed maintenance on mini split system. Washed indoor air filters. Inspected evaporator coils and blower assemblies. Cycled all mini split heads in cooling. Ensured all mini splits head had proper drainage. proceeded to outdoor unit. Check refrigerant pressure and temperature. Inspected outdoor coil and condenser fan. Inspected electrical connections and components on outdoor unit. Mini split system is operating appropriately at this time with all heads supplying appropriate temperature drops.
West Brandywine Township, PA 19320
Review
Boyd Benjamin - West Brandywine Township, PA 19320
Response from DiBiase Heating and Cooling Company:

Hi Boyd! Thank you so much for leaving us a 5-star review!

Review
Explained things well
Robert - West Brandywine Township, PA 19320
Response from DiBiase Heating and Cooling Company:

We are so glad to hear that you had a good experience.

Review
Did not help
Robert - West Brandywine Township, PA 19320
Review
Employee was polite and courteous
Robert - West Brandywine Township, PA 19320
Review
Great job as always.
Phil - West Brandywine Township, PA 19320
Review
Very responsive, tech fixed the problem and explained the path forward. Very professional, did a great job. I’m not happy with the furnace at all, as it has required service multiple times since it was installed.
Jack - West Brandywine Township, PA 19320
Review
Kurt was professional, timely, & friendly.100% satisfactory experience.
Marie - West Brandywine Township, PA 19320
Review
List did a great job as always.
Phil - West Brandywine Township, PA 19320
Request Service
servicedetailscustomerreturningschedule
*
Details Regarding Your Request...
Optional: Drag and drop photos and/or videos:
Max. file size: 4 MB.
Your Contact and Service Location...
*
*
To Serve You Best...
Have we served you in the past?
Yes
No
*
What Is Convenient For You?
*
What time of day is best for you?
First Available
Morning
Afternoon
*

Call For Same Day Service/Emergencies at 610-873-1244 .

By pressing Submit I agree to receive phone, email, or text messages from DiBiase Heating and Cooling Company to the provided mobile number and also agree to the DiBiase Heating and Cooling Company terms and privacy policy. Message & data rates may apply. Consent is not a condition of purchase. We will never share your personal information with third parties for marketing purposes.
Back Next